- NFPA 101 §7.9
- UL 924
- 90-minute battery
- 1 fc avg · 0.1 fc min
- Test: 30 s monthly · 90 min yearly
When normal power fails, the way out of the building has to stay lit for 90 minutes. You can get there with separate emergency fixtures, or you can build the battery into the lights that are already on the drawing. Here is how both routes work with LeonLite fixtures, and where each one fits.
01What the inspector checks
NFPA 101, the Life Safety Code, asks for emergency lighting along the means of egress for at least 90 minutes after normal power fails: at least 1 footcandle on average and 0.1 at any point, measured at the floor, when it starts. Battery equipment gets a 30-second test every month and a full 90-minute test once a year, with written records. The equipment is listed to UL 924. Your local authority having jurisdiction has the final word on where it goes.


02Two routes


03Route A: the battery rides inside
The emergency driver and battery are built into the fixture. One part number, one install, nothing extra above the ceiling. Pick by the space:
| Space | Fixture | Output | Settings | |
|---|---|---|---|---|
| Offices, open ceilings | LinearLux™ EM z2099 | 4,600 lm | 40 W · 3000/4000/5000K | By quote |
| Tall ceilings | LinearLux™ HO EM z2100 | up to 6,900 lm | 40/50/60 W · 3000/4000/5000K | By quote |
| Long rooms | LinearLux™ Spread EM z2101 | 9,200 lm, 8 ft | 80 W · 3000/4000/5000K | By quote |
| Corridors, back rooms | Emergency™ Pendant z1829 | up to 5,200 lm | 25/30/40 W · 3500/4000/5000K | In store |
| Stairwells | Emergency™ Linear z1828 | up to 6,500 lm | Wall mount · damp location | In store |
| Garages, wash bays | Vapor Tight EM z2102 | up to 9,100 lm | 50/60/70 W · 4000/5000/6000K | By quote |
| Parking, loading docks | Vapor Tight EM 8 ft z2103 | up to 15,000 lm, 8 ft | 80/100/120 W · 4000/5000/6000K | By quote |
| Warehouses | Linear High Bay EM z2095 | 30,375 lm | 225 W · 5000K · suspended | By quote |
Every fixture in this table runs 90 minutes on battery and dims 0–10V. The Emergency™ Pendant and Emergency™ Linear carry UL 924 emergency drivers; the Pendant has a test button on the fixture.
LinearLux™ EMBy quotez2099 · 4 ft · 40 W · 4,600 lm · 90-min battery inside
Emergency™ Pendantz1829 · 4 ft · 25/30/40 W · up to 5,200 lm · UL 924 driver
Vapor Tight EMBy quotez2102 · 4 ft · 50/60/70 W · up to 9,100 lm · 90-min battery
Linear High Bay EMBy quotez2095 · 225 W · 30,375 lm · 5000K · 90-min battery
Battery LinearLux does not link with standard LinearLux. Give it its own feed.
Most battery fixtures also want an unswitched hot, so they keep charging when the room switch is off and can tell a switched-off room from an outage. Follow the wiring diagram in each manual.
04Route B: add a battery to the fixture you already picked

Emergency™ ExPower is a 90-minute emergency power supply that installs inline, on the AC side of a fixture. 100–347 V input. It works with 0–10V fixtures up to 150 W, and comes in 15 W (z1721) and 30 W (z1722).
Use it when the fixture is already specified, or already hanging, and plan review asks for emergency coverage at that spot.
05Which route?
| Battery inside | Battery added (ExPower) | |
|---|---|---|
| Parts per location | 1 | 2 |
| Best for | New layouts, with the emergency spots on the plan | Fixtures already chosen or already installed |
| Above the ceiling | Nothing extra | One supply box, about 12 in long |
| Fixture choice | The EM models in the table | Your 0–10V fixture, up to 150 W |
| Battery runtime | 90 min | 90 min |
Before you call for inspection
- Emergency fixtures marked on the reflected ceiling plan
- Battery LinearLux on its own feed
- Unswitched hot wherever the manual calls for one
- Batteries fully charged before the 90-minute test (charge time is in the manual)
- First 30-second test done and logged
- Test log handed to the owner
Lights in this article
LinearLux™ EM z20994 ft · 40 W · 4,600 lm · 90-min battery insideRequest a quote →
LinearLux™ HO EM z21004 ft · 40/50/60 W · up to 6,900 lm · 90-min batteryRequest a quote →
LinearLux™ Spread EM z21018 ft · 80 W · 9,200 lm · 90-min batteryRequest a quote →
Emergency™ Pendant z18294 ft · 25/30/40 W · up to 5,200 lm · UL 924 driverView →
Emergency™ Linear z18284 ft stairwell wall light · up to 6,500 lm · UL 924 driverView →
Vapor Tight EM z21024 ft · 50/60/70 W · up to 9,100 lm · 90-min batteryRequest a quote →
Vapor Tight EM 8 ft z21038 ft · 80/100/120 W · up to 15,000 lm · 90-min batteryRequest a quote →
Linear High Bay EM z2095225 W · 30,375 lm · 5000K · 90-min batteryRequest a quote →
Emergency™ ExPower z172115 W or 30 W · 100–347 V in · 90 min · inlineView →

Justin L.
B2B Sales Manager
Contact a sales manager
Mark the emergency spots on your plan and send it.
I’ll match each spot to a fixture or an ExPower, then quote it.
- Email Justinjustin.l@leonlite.comPlans, schedules, spec questions
- Call or text(949) 279-7251Mon–Fri 8:30 AM–4 PM PT
- Main line800-990-7688LeonLite Commercial · Eastvale, CA














Compartir:
Cómo la realidad aumentada en el diseño de iluminación ayuda a los contratistas a visualizar la iluminación comercial antes de instalarla
Illinois Fluorescent Ban: T5, T8 and Pin-Base CFL Sales End Jan 1, 2027