• NFPA 101 §7.9
  • UL 924
  • 90-minute battery
  • 1 fc avg · 0.1 fc min
  • Test: 30 s monthly · 90 min yearly

When normal power fails, the way out of the building has to stay lit for 90 minutes. You can get there with separate emergency fixtures, or you can build the battery into the lights that are already on the drawing. Here is how both routes work with LeonLite fixtures, and where each one fits.

90 minon battery, every fixture in this article
30 stest, every month
90 mintest, every year
100–347 Vinput on Emergency™ ExPower

01What the inspector checks

NFPA 101, the Life Safety Code, asks for emergency lighting along the means of egress for at least 90 minutes after normal power fails: at least 1 footcandle on average and 0.1 at any point, measured at the floor, when it starts. Battery equipment gets a 30-second test every month and a full 90-minute test once a year, with written records. The equipment is listed to UL 924. Your local authority having jurisdiction has the final word on where it goes.

Timeline: power fails, emergency lighting runs at least 90 minutes on battery, then recharges; tested 30 seconds monthly and 90 minutes yearlyTimeline: power fails, emergency lighting runs at least 90 minutes on battery, then recharges; tested 30 seconds monthly and 90 minutes yearly

02Two routes

Route A: battery and emergency driver built into the fixture. Route B: an ExPower emergency supply added inline on the AC side of a standard fixtureRoute A: battery and emergency driver built into the fixture. Route B: an ExPower emergency supply added inline on the AC side of a standard fixture

03Route A: the battery rides inside

The emergency driver and battery are built into the fixture. One part number, one install, nothing extra above the ceiling. Pick by the space:

Space Fixture Output Settings
Offices, open ceilings LinearLux™ EM z2099 4,600 lm 40 W · 3000/4000/5000K By quote
Tall ceilings LinearLux™ HO EM z2100 up to 6,900 lm 40/50/60 W · 3000/4000/5000K By quote
Long rooms LinearLux™ Spread EM z2101 9,200 lm, 8 ft 80 W · 3000/4000/5000K By quote
Corridors, back rooms Emergency™ Pendant z1829 up to 5,200 lm 25/30/40 W · 3500/4000/5000K In store
Stairwells Emergency™ Linear z1828 up to 6,500 lm Wall mount · damp location In store
Garages, wash bays Vapor Tight EM z2102 up to 9,100 lm 50/60/70 W · 4000/5000/6000K By quote
Parking, loading docks Vapor Tight EM 8 ft z2103 up to 15,000 lm, 8 ft 80/100/120 W · 4000/5000/6000K By quote
Warehouses Linear High Bay EM z2095 30,375 lm 225 W · 5000K · suspended By quote

Every fixture in this table runs 90 minutes on battery and dims 0–10V. The Emergency™ Pendant and Emergency™ Linear carry UL 924 emergency drivers; the Pendant has a test button on the fixture.

Battery LinearLux does not link with standard LinearLux. Give it its own feed.

Most battery fixtures also want an unswitched hot, so they keep charging when the room switch is off and can tell a switched-off room from an outage. Follow the wiring diagram in each manual.

04Route B: add a battery to the fixture you already picked

Emergency ExPower LED emergency power supply with flexible conduit lead
Shown: Emergency™ ExPower 15 W · body 315 × 45 × 28 mm

Emergency™ ExPower is a 90-minute emergency power supply that installs inline, on the AC side of a fixture. 100–347 V input. It works with 0–10V fixtures up to 150 W, and comes in 15 W (z1721) and 30 W (z1722).

Use it when the fixture is already specified, or already hanging, and plan review asks for emergency coverage at that spot.

05Which route?

Battery inside Battery added (ExPower)
Parts per location 1 2
Best for New layouts, with the emergency spots on the plan Fixtures already chosen or already installed
Above the ceiling Nothing extra One supply box, about 12 in long
Fixture choice The EM models in the table Your 0–10V fixture, up to 150 W
Battery runtime 90 min 90 min

Before you call for inspection

  • Emergency fixtures marked on the reflected ceiling plan
  • Battery LinearLux on its own feed
  • Unswitched hot wherever the manual calls for one
  • Batteries fully charged before the 90-minute test (charge time is in the manual)
  • First 30-second test done and logged
  • Test log handed to the owner

Lights in this article

Justin L., B2B Sales Manager at LeonLite Commercial

Justin L.

B2B Sales Manager

Contact a sales manager

Mark the emergency spots on your plan and send it.

I’ll match each spot to a fixture or an ExPower, then quote it.

Request a quoteSpec sheets & manuals